CB-7012, CB-7014, CB-7017 Users Manual
2.39 ~AA2
Description: Read Host Watchdog Timeout Interval
Syntax: ~AA2[CHK](cr)
~ Delimiter character
AA Address of module to read (00 to FF)
2 Command for reading host watchdog timeout interval
Response: Valid Command: !AAVV[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may get no response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of responding module (00 to FF)
VV timeout interval in HEX format, each count for 0.1
second, 01 = 0.1 second and FF = 25.5 seconds
Example:
Command: ~012 Receive: !01FF
Read Address 01 host watchdog timeout interval, return FF,
the host watchdog timeout interval is 25.5 seconds.
Related Command:
Sec.2.36, ~**; Sec.2.40, ~AA3EVV
Related Topic:
Set.3.2, Module Status; Sec.3.3, Dual Watchdog Operation