CB-7012, CB-7014, CB-7017 Users Manual
2.11 $AA8
Description: Read LED Configuration
Note: The command is for CB-7012D/12FD/14D only.
Syntax: $AA8[CHK](cr)
$ Delimiter character
AA Address of module (00 to FF)
8 Command for reading LED configuration
Response: Valid Command: !AAV[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may get no response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of responding module (00 to FF)
V LED configuration
1 = module control, 2 = host control
Example:
Command: $018 Receive: !011
Read Address 01 LED configuration, return module control.
Command: $028 Receive: !012
Read Address 02 LED configuration, return host control.
Related Command:
Sec. 2.12, $AA8V; Sec. 2.13, $AA9(Data)