CB-7012, CB-7014, CB-7017 Users Manual
2.27 @AARL
Description: Read Low Alarm
Note: This command is for CB-7012/12D/12F/12FD/14D only.
Syntax: @AARL[CHK](cr)
@ Delimiter character
AA Address of module (00 to FF)
RL Command for reading low alarm
Response: Valid Command: !AA(Data)[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may get no response.
! Delimiter for valid command.
? Delimiter for invalid command.
AA Address of responding module (00 to FF)
(Data) Low alarm value is in engineering units format.
Example:
Command: @01RL Receive: !0110.000
Read Address 01 low alarm; return 10.000.
Related Command:
Sec. 2.23, @AALO
Related Topic:
Sec. 3.6, High/Low Alarm