CB-7012, CB-7014, CB-7017 Users Manual
2.32 $AA6(SL)(SH)
Description: Set Source Low/High Values for Linear Mapping.
Note: This command is for CB-7014D only.
The data are stored in EEPROM.
Syntax: $AA6(SL)(SH)[CHK](cr)
$ Delimiter character
AA Address of module to set (00 to FF)
6 Command for setting source values
SL Source low level value
SH Source high level value
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may get no response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of responding module (00 to FF)
Example:
Command: $01610.000+10.000 Receive: !01
Set Address 01 source value 10 to +10; return successful.
Related Command:
Sec. 2.30, $AA3; Sec. 2.31, $AA5; Sec. 2.33, $AA7(TL)(TH)
Related Topic:
Sec. 3.8, Linear Mapping