55
CB-7000 DIO Manual
2.23 ~AA5V
Description: Set PowerOn/Safe Value.
Command: ~AA5V[CHK](cr)
~ Delimiter character
AA Address of setting module (00 to FF)
5 Command for set PowerOn/Safe Value
V P = set current output as PowerOn Value, S = set current
output as Safe Value
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may get no response.
! Delimiter for valid Command
? Delimiter for invalid Command
AA Address of response module(00 to FF)
Example:
Command: @01AA Receive: >
Output Address 01 value AA, return successful.
Command: ~015P Receive: !01
Set Address 01 PowerOn Value, return successful.
Command: @0155 Receive: >
Output Address 01 value 55, return successful.
Command: ~015S Receive: !01
Set Address 01 Safe Value, return successful.
Command: ~014P Receive: !01AA00
Read Address 01 PowerOn Value, return PowerOn Value AA.
Command: ~014S Receive: !015500