BASE + C Counter 2 Read | Load
BASE + E None | Counter Control
Interrupt Source Control
The interrupt source is controlled by three bits.
INT2 INT1 INT0 Source
001Pacer - Counter 2
010External - Pin 7
011FIFO Not Empty
100FIFO Half Full
101End of Channel Scan
The A/D trigger source is controlled by two bits.
TS1 TS0 Source
0 X Software Trigger
1 0 Rising Trigger Input, Pin 5
1 1 Pacer - Counter 2
The range of analog input is set by 4 bits.
G3 G2 G1 G0 Range
1000+/- 10 V
0000+/- 5 V (A/D Std.)
0001+/- 2.5 V
0010+/- 1.25 V
01000 to 10 V