Measurement-computing CB-COM-7021 Instrukcja Użytkownika Strona 50

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 76
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 49
50
CB-7021, CB-7022, CB-7024 Users Manual
2.19 $AA4N
Description: Set PowerOn Value for Channel N
Note: The command is for CB-7022 and CB-7024 only.
Syntax: $AA4N[CHK](cr)
$ Delimiter character
AA Address of setting module (00 to FF)
4 Command for setting PowerOn Value, store the current
output value as PowerOn Value.
N Channel to set (0 to 1 for CB-7022, 0 to 3 for CB-7024)
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may not get
response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
Example for CB-7024:
Command: #012+00.000 Receive: >
Set address 01 channel 2 output 0.0, returns successful.
Command: $0142 Receive: !01
Set address 01 channel 2 PowerOn Value, returns successful.
The Power-On Value of channel 2 is set to 0.0 now.
Related Command:
Sec. 2.15 #AAN(Data), Sec. 2.21 $AA7N
Related Topics: