CB-7021, CB-7022, CB-7024 Users Manual
2.11 $AA4
Description: Set PowerOn Value
Note: The command is for CB-7021/21P only.
Syntax: $AA4[CHK](cr)
$ Delimiter character
AA Address of setting module (00 to FF)
4 Command for setting PowerOn Value. Store the current
output value as PowerOn Value.
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
Example:
Command: #0100.000 Receive: >
Set address 01 output 0.0 mA, returns successful.
Command: $014 Receive: !01
Set address 01 PowerOn V alue, returns successful. The
module 01 will go to 0.0 mA with module power on.
Related Command:
Sec. 2.7 #AA(Data)
Related Topics:
Sec. 3.5 Analog Output