CB-7011/CB-7011D, CB-7018 Users Manual
2.20 ~AAEV
Description: Enable/Disable Calibration
Syntax: ~AAEV[CHK](cr)
~ delimiter character
AA address of setting module (00 to FF)
E command for enable/disable calibration
V 1=enable calibration, 0=disable calibration
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may get no
response.
! delimiter for valid command
? delimiter for invalid command
AA address of response module(00 to FF)
Example:
Command: $010 Receive: ?01
Perform address 01 span calibration, return it is not ready for
calibration.
Command: ~01E1 Receive: !01
Set address 01 to enable calibration, return success.
Command: $010 Receive: !01
Preform address 01 span calibration, return success.
Related Command:
$AA0 (Sec. 2.5), $AA1 (Sec. 2.6)
Related Topic:
Calibration (Sec. 1.9)