CB-7011/CB-7011D, CD-7018 Users Manual
2.7 $AA2
Description: Read Configuration
Syntax: $AA2[CHK](cr)
$ delimiter character
AA address of reading module (00 to FF)
2 command for reading configuration
Response: Valid Command:
!AATTCCFF[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
! delimiter for valid command
? delimiter for invalid command
AA address of response module(00 to FF)
TT type code of module (reference Sec. 1.10)
CC baudrate code of module (reference Sec. 1.10)
FF data format of module (reference Sec. 1.10)
Example:
Command: $012 Receive: !01050600
Read address 01 configuration, return success.
Command: $022 Receive: !02030602
Read address 02 configuration, return success.
Related Command:
%AANNTTCCFF (Sec. 2.1)
Related Topics:
Config. Tables (Sec. 1.10), INIT* pin Operation (Sec. 3.1)