Measurement-computing UL for NI LabVIEW Instrukcja Użytkownika Strona 18

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 109
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 17
Universal Library Virtual Instruments (VIs) Analog Input VIs
Range input values
Range Input value Range Input value
±20 V 27 0 to 5 V 14
±10 V 1 0 to 4 V 36
±5 V 2 0 to 2.5 V 15
±4 V 28 0 to 2 V 16
±2.5 V 3 0 to 1.67 V 17
±2 V 29 0 to 1.25 V 18
±1.67 V 4 0 to 1 V 19
±1.25 V 5 0 to 0.5 V 32
±1 V 6 0 to 0.25 V 33
±0.625 V 7 0 to 0.2 V 34
±0.5 V 8 0 to 0.1 V 20
±0.25 V 30 0 to 0.01 V 21
±0.2 V 31 0 to 0.02 V 35
±0.1 V 9 4 to 20 mA 22
±0.05 V 10 0 to 20 mA 26
±0.01 V 11 2 to 10 mA 23
±0.005 V 12 1 to 5 mA 24
0 to 10 V 13 0.5 to 2.5 mA 25
DataValue Value of A/D measurement in binary counts. Use ToEng.VI (on page 48) to
convert into engineering units (volts or milliamps).
ErrCode Error code returned from the Universal Library. Zero if no error occurred. Use the
ErrMsg VI (on page 97) to convert
ErrCode into a readable string.
18
Przeglądanie stron 17
1 2 ... 13 14 15 16 17 18 19 20 21 22 23 ... 108 109

Komentarze do niniejszej Instrukcji

Brak uwag