CB-7013, CB-7033 Users Manual
2.14 ~AAO(Data)
Description: Set Module Name
Syntax: ~AAO(Data)[CHK](cr)
~ Delimiter character
AA Address of setting module (00 to FF)
O Command for set module name
(Data) New name for module, maximum six characters
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
! Delimiter for valid command.
? Delimiter for invalid command.
AA Address of response module (00 to FF).
Example:
Command: ~01O7013 Receive: !01
Set address 01 module name to 7013, returns successful.
Command: $01M Receive: !017013
Read address 01 module name, returns 7013.